Your Tankless Flush Schedule Depends on Which Sherman Water You Get

How often to flush a tankless water heater in Sherman comes down to which city supply reaches your tap. The treated Lake Texoma water tested 124 ppm total hardness in the city’s 2025 report, which the USGS scale calls hard, so a yearly flush is the sensible setting there. The well water tested between 4.30 and 22.90 ppm, soft enough to stretch the interval, but it carries dissolved solids that the heater manuals set their own limits on.

TL;DR

A tankless water heater flush clears mineral scale out of the heat exchanger, the part that carries the longest warranty and costs the most to replace. Neither Rinnai nor Navien prints one fixed interval. Both build a service reminder into the unit that the installer sets at six months, one year, or two years depending on the water. On Sherman’s Lake Texoma supply, measured at 124 ppm hardness in the City of Sherman 2025 water quality report, a one-year reminder fits most households and six months fits a heater set hot or run hard. The city’s well supply tested 22.90 ppm hardness at most, so scale builds slowly there, but total dissolved solids reached 888 ppm in the 2023 sampling, above the 500 mg/L guideline both manufacturers print. Skipping flushes can cost the heat exchanger warranty.

Which Water Reaches Your Tap Sets the Interval

Sherman does not run one water supply. The city’s own Sherman 2025 Annual Water Quality Report says the water “comes from Lake Texoma, which is surface water and one or more of twenty-two ground water wells that are located throughout the City of Sherman.” Those two sources could hardly be more different for a tankless heater.

Here are the figures that matter, lifted from the secondary contaminants table on page 15 of that report. Each value is the highest level detected, and the collection year is the one the city printed beside it.

What was measured

Lake Texoma surface water

Sherman groundwater (wells)

Total hardness as calcium carbonate

124 ppm (2025)

4.30 to 22.90 ppm (2025)

Total dissolved solids

319 ppm (2025)

389 to 888 ppm (2023)

Chloride

89.7 ppm (2025)

16.5 to 227 ppm (2023)

Sodium

66.80 ppm (2025)

238 to 604 ppm (2025)


Read across that table, and the problem splits in two. Lake water is the hard one. Well water is the soft one with a lot of other material dissolved in it.

If you are not sure which one you get, our older write-up on how the city’s two supplies split across town covers the separation line the city’s 2023 report described. The 2025 report no longer prints that sentence, so treat any map as a starting point. A hardness test strip dipped in a glass of cold tap water settles in a minute: a reading near the top of the scale points to the lake, and one near zero points to the wells.

Living in Denison, Pottsboro, Howe, Whitesboro, or out in the county? These numbers belong to Sherman’s system only. Pull the report from whoever sends your water bill, because the interval follows your water rather than your zip code.

What Does the Heater’s Own Reminder Say?

Two of the major tankless brands, Rinnai and Navien, answer the frequency question the same way: with a timer the installer sets, not a number printed in the manual. The Rinnai RE series installation manual offers a Service Soon reminder with four settings: disabled, half a year, one year, or two years. The manual says the choice is the “installer’s preference based on water conditions.”

Navien’s NPE installation manual carries the same idea under a different name. Its Lime Alarm can be set to alert at 6, 12, or 24 months, and when the period runs out, the display shows error 760, which Navien’s operation manual describes as a “Flushing/service alarm.”

So the question to ask about your own heater is simple. What did the installer set it to, and was that choice made for your water or left at whatever the box shipped with?

The code that means it is already late

Rinnai heaters also watch for scale directly. When buildup in the heat exchanger starts to affect performance, the controller shows an LC code, and the manual’s instruction is blunt: flush the heat exchanger to prevent damage. A timer reminder is maintenance. An LC code is the heater telling you it waited too long.

What you see

Brand

What it means

SS on the controller

Rinnai

The service interval you set has run out

LC on the controller

Rinnai

Scale is already affecting performance

Error 760

Navien

The lime alarm period has been reached

The Line the Manuals Draw on Water Quality

Both manufacturers print a table of what their heat exchanger can live with. The Rinnai RE manual, in its water quality guidelines, lists total hardness up to 200 mg/L, total dissolved solids up to 500 mg/L and chlorides up to 250 mg/L. Navien’s NPE installation manual prints the same three ceilings, adding that 200 mg/L is 12 grains per gallon. One ppm and one mg/L are the same measure in water, so the city’s figures drop straight into the comparison.

Guideline in the manuals

Ceiling

Lake Texoma supply

Sherman wells

Total hardness

200 mg/L

124, under

22.90 at most, well under

Total dissolved solids

500 mg/L

319, under

up to 888, over at the high end

Chloride

250 mg/L

89.7, under

up to 227, close at the high end

Rinnai’s wording on what happens past those lines is direct: water with chemicals exceeding the listed levels “can damage the Rinnai Tankless Water Heater,” and “replacement of components due to water quality damage is not covered by the warranty.” Navien says the same thing more briefly.

Why soft water does not mean skip it

This is the part every national flush guide misses, and it is the part that matters on the well supply. People on well water hear “soft” and assume a tankless heater never needs a visit. The hardness figure backs them up. The dissolved solids figure does not.

At 888 ppm in the 2023 sampling, the well supply’s highest dissolved solids reading ran well past the 500 mg/L both manuals print. The range started at 389, so not every well and not every day sits at the top. We cannot tell you from a report which well feeds your block on a given week, and neither can anyone else.

What we can say is that a heater on well water should still be opened and looked at on a schedule. On this kind of water, the two-year reminder is the setting we would pick: low scale, but a supply worth checking.

If you want a second opinion on your own supply, a basic dissolved solids meter reads in seconds at the tap. It will not tell you what those solids are, but a reading well under the manual’s 500 mg/L line is one less thing to wonder about.

Sherman lake and well water hardness compared with tankless heater manual limits

Is Lake Texoma Water Hard Enough to Scale a Heat Exchanger?

Yes. The USGS guide to water hardness classifies 121 to 180 mg/L as calcium carbonate as hard, and Sherman’s surface supply tested 124. That sits at the bottom of the hard band rather than the top, but it is still hard water, and the USGS says plainly what happens when hard water is heated: solid deposits of calcium carbonate form, which can shorten equipment life and raise heating costs.

A tank heater collects that scale as sediment on its floor. A tankless heater has no floor. It pushes every gallon through narrow passages in a heat exchanger, so the scale coats the passages themselves.

The number has moved, too. Our older articles quoted higher lake readings from earlier city reports, and the 2025 report brings the surface figure down to 124. That is good news for anyone on lake water, but it does not change the recommendation, because 124 is still inside the USGS hard range.

Hotter Settings Scale Faster, and Cost Warranty

Temperature is the lever most owners never touch. The Rinnai manual states that scale build-up “can be accelerated if the water heater is set at a high temperature,” and the warranty terms put a number on the other risk.

For a residential install, Rinnai covers the heat exchanger for 15 years or 12,000 combustion hours, whichever comes first. Set the unit above 160 degrees Fahrenheit, and that coverage drops to 8 years.

A quick check on your own unit:

  • Look at the set temperature on the controller
  • If it reads above 160, ask whether anything in the house actually needs that
  • On lake water with a high setting, move the reminder from one year to six months
  • Write the date of the last flush on a label on the unit

That last item costs nothing and saves a lot of guessing later.

What a Flush Actually Involves

A flush is not the same job as draining a tank. The Rinnai RE manual lays out the procedure in fifteen steps, and the core of it looks like this:

  1. Shut off power and close the hot and cold shutoff valves
  2. Connect a circulation pump to the service isolation valves
  3. Pour four gallons of undiluted, food-grade white vinegar into a pail
  4. Circulate it through the heat exchanger for at least one hour at four gallons per minute
  5. Rinse with fresh water for five minutes
  6. Pull and clean the inlet water filter, then restore water and power

Navien’s operation manual opens its own flushing section with a caution that calls it “a somewhat complicated procedure” and warns that improper maintenance can void the warranty. Rinnai recommends isolation valves be installed specifically so this job can be done.

Can you do it yourself?

With isolation valves already fitted, a handy owner with a pump and hoses can follow those steps. Where the valves are missing, the inlet filter is seized, or the controller is already showing LC or 760, it stops being a weekend job. That is usually the point to book tankless water heater repair rather than keep guessing at a heater that is already telling you something is wrong.

One more thing people ask about. A tank heater has the sacrificial rod inside a tank heater to check, as well as sediment to drain. A tankless unit has no anode, so the flush and the filter clean are most of the maintenance job.

What Skipping It Costs Under the Warranty

The flush is cheap next to the part it protects. Rinnai’s warranty list of what is not covered includes “improper maintenance (such as but not limited to scale build-up, freeze damage, or vent blockage)” and “any damage caused by poor water quality.” Its flushing section is shorter still: “Damage caused by lime build-up is not covered by the water heater’s warranty.”

Navien’s residential warranty excludes “failure to perform regular maintenance.” The heat exchanger carries the longest coverage on both brands, and a missed flush is what puts it at risk. Keep a dated record of every service.

Softener, Conditioner, or Neither?

This depends entirely on which side of the table you sit.

On lake water: Rinnai’s manual says water in a hard water area “must be treated and may require a more frequent flushing schedule,” and it sells its own scale conditioning system for that reason. A softener or a scale inhibitor on the cold line is a reasonable add-on for a heater in heavy use at 124 ppm. It stretches the time between flushes. It does not remove the need for them.

On well water: A softener exists to remove hardness, and at 22.90 ppm at most, there is little hardness to remove. It will not lower dissolved solids, so it answers a question the well supply is not asking. Spend that money on keeping the flush and inspection schedule instead.

Outside Sherman, the answer can flip either way. Homes we look after in Van Alstyne and the surrounding area are usually served by a different water system, and the right call there starts with that supplier’s own report, not with Sherman’s.

Set the Reminder Before Winter, Then Book the Flush

Here is the practical version. Check which Sherman supply you are on, check what the reminder on your heater is set to, and match the two: one year on lake water, six months if it runs hot or hard, and no longer than two years on well water. If you have never flushed the unit, or you cannot remember when it was last done, that is your answer on timing too.

Fall is a sensible moment to do it, before cold snaps put an outdoor unit’s freeze protection to work and before a house fills up with holiday guests. It sits well alongside the rest of our fall checklist for the weeks before the holidays.

If the controller is already showing a code, or you would rather hand the pump and hoses to someone else, Ironclad Plumbing can flush the heat exchanger, clean the inlet filter, and reset the reminder to suit your water.

Frequently Asked Questions

How often should I flush a tankless water heater in Sherman?

On Sherman’s Lake Texoma supply, which tested 124 ppm hardness in 2025, once a year suits most homes and every six months suits a heater set hot or used heavily. The city’s softer well supply can stretch to two years, and no longer.

Rinnai’s manual says LC appears when scale in the heat exchanger has begun to affect performance. The instruction is to flush the heat exchanger to prevent damage, then reset the code. It means the flush is overdue, not just due.

Navien lists error 760 as the flushing and service alarm. It appears when the lime alarm period the installer chose, 6, 12, or 24 months, has run out. It is a reminder rather than a fault, and the unit needs servicing.

No. Sherman’s wells tested soft on hardness, but total dissolved solids reached 888 ppm in the 2023 sampling, above the 500 mg/L guideline Rinnai and Navien print. The heater still needs a scheduled flush and inspection.

It can. Rinnai excludes damage from scale build-up and poor water quality, and Navien excludes failure to perform regular maintenance. Keeping a dated record of each flush protects the heat exchanger coverage, the longest on both brands.